Altitude(ft) Pressure   Cooling & Dehumidifying  
  14.696 psia   Total Cooling Btu/hr   36,110  
  Sensible Cooling Btu/hr   26,564 Includes heat removed from condensate
    Entering Air   Latent Cooling Btu/hr   9,546
      Tons of Cooling   3.01
Dry Bulb   Wet Bulb   Relative Humidity Dew Point Grains of Moisture CFM per Ton   398.8  
    51.1 % 60.37° 78.19 /lb   Sensible Heat Ratio   0.74  
  Dry Bulb TD   20°  
        Leaving Air     Enthalpy Difference   6.71 Btu/lb  
            Mass Air Flow Rate   5413.21 lb/hr 90.22 lb/min
Dry Bulb   Wet Bulb   Relative Humidity Dew Point Grains of Moisture CFM Entering Coil   1249.5 ft³/min  
    86.29 % 55.96° 66.54 /lb   Apparatus Dew Point   54.6°
  Bypass Factor   0.21
        Condensation Rate   9.01 lb/hr 2.4 oz/min
          Condensate Water Temp   55.6° approximate
        Entering Leaving        
          0.073 lb/ft³ 0.0759 lb/ft³ Density (ρ)
          31.45 Btu/lb 24.74 Btu/lb Enthalpy of moist air (h)
          0.01117 lb/lb 0.00951 lb/lb Humidity ratio (W)
          13.849 ft³/lb 13.301 ft³/lb Specific volume (v)
          50.223 % 86.084 % Degree of saturation (μ)
          0.02224 0.01104 Humidity ratio of saturated air (Ws)
          0.01419 0.01008 Humidity ratio of saturated air at wb (Ws*)
          0.25927 psia 0.22121 psia Partial pressure of water vapor (Pw)
          0.50735 psia 0.25634 psia Water vapor pressure at saturation (Pws)
          0.32772 psia 0.23439 psia Water vapor pressure saturated at wb (Pws*)
  1059.43 Btu/lb   Enthalpy of latent heat of water vapor at condensing temperature
  1087.8 Btu/lb   Enthalpy of saturated water vapor at condensing temperature
  28.37 Btu/lb   Enthalpy of saturated liquid at condensing temperature
  23.6 Btu/lb Enthalpy of saturated liquid at final temperature